A. Example of the use of the shielded cable in a single coolant system (Setting of addresses is necessary)
Example of control line wiring
1) Standard
OS
OC
(52)
(51)
TB3
TB3
TB7
M1 M2
S
M1M2
M1M2 S
Shielded cable
One remote control unit for each indoor unit.
Within ( ): Address
2) 2 Remote control operation
OS
OC
(52)
(51)
TB3
TB3
TB7
M1 M2
S
M1M2
M1M2 S
Shielded cable
2 remote control units for 1 indoor
unit.
3) Group operation
OS
OC
(52)
(51)
TB3
TB3
TB7
M1 M2
S
M1M2
M1M2 S
Shielded cable
Operation of multiple indoor units with 1 remote controller.
1) ~ 3) above can be combined.
28
L
L
1
2
IC
(01)
TB5
TB13
TB5
M1M2 S
1 2 3
M1M2 S
TB6
(102)
TB6
RC
(101)
RC
IC
(01)
TB5
TB13
TB5
M1M2 S
1 2 3
M1M2 S
TB6
TB6
TB6
(101)
(151)
(102)
RC
RC
RC
(Main remote
(Sub remote
(Main remote
controller)
controller)
controller)
IC (Main)
(01)
TB5
TB13
TB5
M1M2 S
1 2 3
M1M2 S
TB6
(101)
RC
Wiring method, address setting
a. Run the wire to terminals M1 and M2 the variable capacity
unit (OC) transmission line terminal block (TB3) and to ter-
minals M1 and M2 on the constant capacity unit (OS) trans-
mission line terminal block (TB3) as well as to the terminals
M1 and M2 of the transmission line terminal block (TB5) of
each indoor unit (IC). (Two-wire, no polarity)
IC
Also, run the shielded ground wire to the ground terminal
of the variable capacity unit, the S terminal of the constant
(02)
capacity unit (TB3), and the S terminal of each indoor unit
(TB5).
TB13
1 2 3
b. Connect the wires to terminals M1 and M2 of the transmis-
sion line terminal block (TB5) in each indoor unit (IC) and
connect them to the remote control (RC) terminal block (TB6).
c. Set the address setting switch as shown in the following ta-
ble.
Unit
Indoor unit
Remote control
Variable capacity
unit
Constant capacity
unit
Note 1. If the address of the variable capacity unit or the constant capac-
ity unit is set at 100, set one of the address switches at 01 ~ 50.
Note 2. It is not necessary to set the 100's position in the remote control
unit.
a. Same as above
b. Same as above
c. Set the address setting switch as shown in the fol-
IC
lowing table.
(02)
Unit
TB13
Indoor unit
1 2 3
Main remote
controller
Sub remote
controller
Variable capacity
unit
TB6
(152)
Constant capacity
unit
RC
(Sub remote
Notes 1, 2. Same as above
controller)
a. Same as above
b. Connect terminals A and B (M1 and M2) of the trans-
mission line terminal block (TB5) of the indoor unit
(IC Main) with the lowest address of all the indoor
units (IC) in the same group and the terminals on
IC (Sub)
the remote control (RC) terminal block (TB6).
c. Set the address setting switch as shown in the fol-
(02)
lowing table.
d. Within the same group, let the indoor unit (IC) which
TB13
1 2 3
functions the most be the IC (Main) unit.
Unit
IC (Main)
IC (Sub)
Main remote
controller
Sub remote
controller
Variable capacity
unit
Constant capacity
unit
Notes 1, 2. Same as above
Range
Setting method
01 to 50
101 to 150
Indoor unit address + 100
Note 2
The smallest address of
51 to 100
the indoor units + 50
Note 1
Variable capacity unit ad-
51 to 100
dress + 1
Note 1
Range
Setting method
01 to 50
101 to 150
Indoor unit address + 100
Note 2
151 to 200
Indoor unit address + 150
Note 2
The smallest address of the
51 to 100
indoor units + 50
Note 1
Variable capacity unit ad-
51 to 100
dress + 1
Note 1
Range
Setting method
Address of the indoor unit
with the smallest address of
01 to 50
all the indoor units in the
same group
Address of any of the indoor
units except the address of the
01 to 50
IC (Main)
Let the number be in sequence
with that of the IC (Main)
Address of the IC (Main) in
101 to 150
Note 2
the same group + 100
151 to 200
Address of the IC (Main) in
Note 2
the same group + 150
51 to 100
The smallest address of the
Note 1
indoor units + 50
51 to 100
Variable capacity unit ad-
Note 1
dress + 1