10.6. How to install branch pipe

For detail, please observe the instruction manual attached to the op-
tional refrigerant branch kit.
Joint
A
A To outdoor unit
B To branch piping or indoor unit
Apart from the CMY-Y202-F and CMY-Y302-F gas side, there are no
restrictions on the posture for attaching joints.
Ensure that the branch pipes for the CMY-Y202-F and CMY-Y302-F
gas side are attached horizontally or facing upwards (see the dia-
gram below).
Horizontal
Within ±15°
There is no limitation on the joint mounting configuration.
If the diameter of the refrigerant piping selected by the procedures
described on pages 13 to 14 is different from the size of the joint,
match the sizes using a deformed joint. The deformed joint is included
with the kit.
Header
A
A To outdoor unit
B To indoor unit
No restriction is applied to the mounting posture of the header.
If the diameter of the refrigerant piping selected using the proce-
dures described on pages 14 and the size of the joint is different,
match the sizes using a deformed joint. The deformed joint is included
with the kit.
20
B
Facing upwards
(Facing downwards is not possible)
Within ±15°
Within ±15°
B
C
C Pipe cutter
D or
E Deformed joint
When the number of pipes to be connected is smaller than the number
of header branches, install a cap to the unconnected branches. The
cap is included with the kit.
Distributer (liquid)
Field piping
Field piping
Variable
Variable
capacity unit
capasity unit
Mount the distributor (liquid, optional CMC-30A) so that it is within
±15° in relation to the horizontal plane (see figure above).
D
E
±15°
Constant
Constant
capacity unit
capasity unit