Connection and function of the switching outputs
Switching outputs
The.S80.door.control.has.2.potential-free.relay.switching.outputs.(changeover.contacts,.see.wiring.diagram),.each.with.a.
switching.capacity.of.250.V.AC./.5.A.
ELS Professional Card 3.1
The.two.relays.on.the.ELS.Professional.Card.3.1.have.different.switching.functions.depending.on.the.position.of.DIP.switches.
1.5,.1.6.and.1.7.in.accordance.with.the.following.table.
Switching functions of the indicator outputs
Door status
Relay.1.switches.on.at.the.top.door.end.limit.
Relay.2.switches.on.at.the.bottom.door.end.limit.
In.the.event.of.door.movement,.both.relays.are.off.
Traffic lights + yard light with time delay
Relay.1.switches.on.at.the.top.door.end.limit.
(traffic.light.red/green.via.changeover.contacts)..
At.the.beginning.of.each.door.movement.relay.2.switches.on.and.remains.on.-.at.the.end.
of.each.door.movement.it.switches.off.after.a.delay.of.120s.(time.Z6).
Traffic lights + yard light control pulse
Relay.1.switches.on.at.the.top.door.end.limit.
(traffic.light.red/green.via.changeover.contacts)...
At.the.beginning.of.each.door.movement.relay.2.switches.on.for.1s.
(passing.contact,.pulse.to.actuate.a.time-delay.relay).
Warning light + yard light with time delay
Relay.1.switches.on.when.the.door.leaves.either.of.the.end.limits.and.remains.on.
At.the.beginning.of.each.door.movement.relay.2.switches.on.and.remains.on.-.120s.
(time.Z6).after.the.end.of.each.door.movement.it.switches.off.after.a.delay.
If.automatic.closing.has.been.set,.the.two.relays.switch.on.as.soon.as.the.early.warning.
time.(3.s,.time.Z3).begins.
Warning light flashing + yard light pulse
Relay.1.switches.on.when.the.door.leaves.either.of.the.end.limits.and.flashes.at.a.rate.of.
1.Hz.
At.the.beginning.of.each.door.movement.relay.2.switches.on.for.1s.
(passing.contact,.pulse.to.actuate.a.time-delay.relay).
If.automatic.closing.has.been.set,.the.two.relays.switch.on.as.soon.as.the.early.warning.
time.(3.s,.time.Z3).begins.
Warning light flashing + yard light with time delay and early warning
Relay.1.switches.on.3.s.(early.warning.time.Z3).before.the.door.leaves.either.of.the.end.
limits.and.remains.on.
Relay.2.switches.on.3.s.(early.warning.time.Z3).before.beginning.each.door.movement.
and.remains.on.-.at.the.end.of.each.door.movement.it.switches.off.with.a.delay.of.120s.
(time.Z6).
Warning light flashing + yard light control pulse, with early warning
Relay.1.switches.on.for.3.s.(early.warning.time.Z3).before.the.door.leaves.either.of.the.
end.limits.and.flashes.at.a.rate.of.1.Hz.
Relay.2.switches.on.3.s.(early.warning.time.Z3).before.the.beginning.of.each.door.move-
ment.for.1.s.(passing.contact,.pulse.to.actuate.a.time-delay.relay).
DIP 1.5
DIP 1.6
DIP 1.7
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
OFF
OFF
ON
ON