Fault diagnosis
7.2
Troubleshooting
Problem
Possible cause
No LED
No supply voltage
indication
• Power
• Undervoltage
LED does
• Overvoltage
not flash.
• Sensor
does not
switch.
The sensor
Sensor has been
does not
placed in the safe
switch, also
state (logical "0").
not after
Cause:
removal of
• Cross-circuit
actuation
and
renewed
actuation.
• Cross circuit error
• Error detected in
between the
outputs OUT1 and
OUT2
between one of
the outputs and
the supply voltage
the sensor.
Operating instructions
IN4000 Direct
Rectification of the
error
⋅ Switch the voltage
supply on.
⋅ Check supply
voltage (see 9.1
"Data sheet" on
page 83).
⋅ Switch the voltage
supply off and
back on again.
⋅ Test the
connections and
their wiring.
⋅ Test the
components
connected, e.g.
the PLC.
⋅ Rectify possible
cross-circuits.
⋅ Replace the
device.