The insert has a remote control with display and incorporated ambient probe for measuring the temperature in the
context of the room.
For measuring away from the unit, the installation of a room chronothermostat/thermostat is recommended.
- Installation and assembly must be done by qualified and/or authorized personnel.
- The insert cannot be installed in bedrooms, bathrooms and in general in rooms where
another heating unit is already installed without an independent air inflow.
It is advisable to provide suitable fire-prevention devices for any eventuality.
-
- Do not install the insert in places with an explosive atmosphere.
2.3 Combustion air inlet
In the room where the insert is installed a quantity of air must flow at least equal to that required for combustion; for
this reason must be guaranteed a flow of air, clean and free of pollutants, to satisfy a regular combustion at
maximum power without any hindrance or obstruction of the passage section; must also be drawn in from the
condition that in the vicinity of the insert is practiced an air intake communicating with the outside wall of the free
surface of at least 100 cm ² suitably protected externally by a protection grid to prevent obstructions.
2.4 Fume exhaust
The fumes can be exhausted through a connection to a conventional flue or an external duct with double wall or
insulated pipe. The fume exhaust connections must guarantee a minimum draft of 10 Pa so that the evacuation of
fumes is ensured in case of a temporary power failure.
- The installer must check the efficiency and state of the flue and its conformity with the local, national and
European regulations.
- Certified pipes and connections with adequate seals guaranteeing their tightness must be used.
- Clean the flue and respective connection at least once a year.
Types of installation
Listed below are definitions and requirements for correct installation of an exhaust flue in accordance with Italian
Standard UNI10683:
FLUE: a vertical duct for collecting and expelling, at an appropriate height
from ground, the fumes coming from a single unit and, where permitted,
more than one.
FLUE technical requirements:
- it must be fumetight, isolated and insulated depending on its use;
- it must have a mainly vertical path with axis deviations <45°;
- it must be at a suitable distance from flammable materials with insulation
or air gap;
- it must preferably have a constant, free and independent round internal
section;
- it is advisable for the flue to have an inspectionable chamber for the
collection of solid materials
- and any condensate, placed under the beginning of the fume duct.
The combustion air is drawn through a
PROTECTION GRID complete internal
network located in the proximity of the
installation compartment of the insert
(maximum distance of 1 m. From the
suction pipe). This component is not
present in the air intake kit optional.
Min. distance 0.2 m
44
Electrical
connection
Antiwind
grille
Flue
Flue
connection
Inspectionable
chamber
Ext. Air inlet
min.100 cm
TERMOFIRE L