Floors in wood or in any flammable material must be suitably protected at the base with steel or toughened glass
panels; the protection must cover a certain area in front of the fireplace-insert.
To avoid overheating of the unit, air recirculation with one or more
openings must be created in the upper and lower part of the cladding
inside the fireplace structure covering the entire insert.
The following dimensions must be respected:
- bottom inlet for cold air drawn from the room, total minimum area
500 cm²
- top outlet for natural convection of hot air, total minimum area 450
cm².
The natural air circulation system is completely separate
from the combustion air inlet.
The unit can be installed in an existing fireplace or in a special compartment built to measure and covered with
plasterboard; in any case the optional insert support can be requested.
Distance from
flammable
Reference
A
B
C
D
E
internal
E
external
Flue connection
Inspection door on
flue
Cold air INLET min.
500 cm²
42
Minimum
distance from
materials
flammable
[mm]
materials [mm]
200
50
200
50
1500
800
500
200
200
0
400
-
Hot air OUTLET min. 450 cm²
Combustion air inlet
min. 100 cm²
TERMOFIRE L