Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data Pm 20 - Dehn PM 20 Bedienungsanleitung

Ableiterprüfgerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3. Technical data PM 20

Figure 1 PM 20 tester
6
External supply
- Operating voltage
- Operating current
Displayed only
during measurement
Battery
(not included in delivery)
Test parameters
-Test voltage
-Measuring range
-Resolution
-Test current monitoring
system
Test period
Test output sockets
Measured value indicator
Number of individual tests
in battery operation
Ambient temperature du-
ring operation
Accessory included in
delivery
Serial number
Test adapter
(not included in delivery)
8 ... 12 V DC
1 mA
20 ... 200 mA
9 V IEC6F22 / NEMA-1604-A
"alcaline" batteries preferred
Max. 1200 V DC
- Rise speed
1000 V / sec.
Up to 1100 V
1 V
Automatic detection whether:
-Limitation to reference value
⇒ Test current constant at 1
mA
-Response via ignition
⇒ The test voltage is switched
off
Max. 1.5 sec.
Until the measurement value
is displayed
Safety pole terminals (4 mm)
Negative pole: black
Positive pole: red
LCD, alpha/ numeric, 8-digit
Typically 2000
+10 ... +35°C
2 test cables (1 m each)
2 safety test clips
1 power supply unit (230 V AC)
1 storage bag
Individual
(on the front side)
PA-DRL Part No. 910 507
(for testing DPL 1/10... and
DRL...)
PA-BXT Part No. 910 508
(for testing BLITZDUCTOR XT
and CT)

Werbung