Hitachi RAS-3FSVNE Betriebshandbuch Seite 37

Set free mini
Vorschau ausblenden Andere Handbücher für RAS-3FSVNE:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
Code
Category
No.
11
Inlet Air Thermistor
12
Outlet Air Thermistor
Sensor on
13
Freeze Protection Thermistor
Indoor Unit
14
Gas Piping Thermistor
19
Tripping of Protection Device for Fan Motor
21
High Pressure Sensor
22
Outdoor Air Thermistor
23
Discharge Gas Thermistor on Comp.
24
Evaporating Thermistor
26
Suction Gas Thermistor
29
Low Pressure Sensor
31
Incorrect Setting of Outdoor and Indoor Unit
Sensor on
32
Abnormal Transmission of Other Indoor Unit
Outdoor Unit
35
Incorrect Setting in Indoor Unit No.
36
Incorrect Indoor unit Type
38
Abnormality of Protective Circuit in Outdoor Unit
43
Pressure Ratio Decrease Protection Activating
44
Low Pressure Increase Protection Activating
45
High Pressure Increase Protection Activating
Activation of Low Pressure Decrease Protection
47
Device
51
Abnormality of Current Sensor for Inverter
52
Inverter
Overcurrent Protection Activation
53
Protection Activation of ISPM
54
Inverter Fin Temperature Increase
57
Outdoor Fan
Fan Motor Abnormality
EE
Compressor
Compressor Protection Alarm
Content of Abnormality
TROUBLESHOOTING
Leading Cause
Failure of Thermistor, Sensor, Connection.
Failure of Fan Motor
Failure of Thermistor, Sensor, Connection
Incorrect Setting of Capacity Code.
Failure of Power Supply, PCB in other Indoor Unit.
Failure of other Indoor Unit of the same Refrigerant Cycle
Duplication of Indoor Unit number
Indoor Unit is not for R410A
Failure of Indoor Unit PCB. Incorrect wiring. Connection to PCB
in Indoor Unit.
Failure of Compressor, Inverter
Overload to Indoor in Cooling. High Temperature of Outdoor Air In
Heating Expansion Valve Open Lock
Overload Operation. Excessive Refrigerant. Clogging of Heat
Exchanger
Stoppage by Excessively Decrease of evaporating Temperature
is activated 3 times in one hour, Locked Motor in Heating
Operation.
Failure of Control PCB, ISPM
Failure of ISPM, Clogging of Heat Exchanger, Locked
Compressor
ISPM Abnormality
Failure of Compressor, clogging of Heat Exchanger.
Abnormal Inverter Fin Thermistor.
Clogging of Heat Exchanger
Abnormal Outdoor Fan
Disconnected wire of Incorrect wiring between
Control PCB and Inverter PCB.
Incorrect Wiring or Fan Motor Abnormality
Failure of Compressor.
18
29

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ras-4fsvneRas-5fsvne