Herunterladen Inhalt Inhalt Diese Seite drucken

Outdoor Unit; Indoor Unit - Hitachi RAS-3FSVNE Betriebshandbuch

Set free mini
Vorschau ausblenden Andere Handbücher für RAS-3FSVNE:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 69
11
REFRIGERANT PIPING & REFRIGERANT CHARGE
16
4. After connecting the refrigerant piping, seal the open
space between knockout hole and refrigerant pipes by
using insulation material.
Unit
Side
5. Operation of stop valve should be performed according
to the figure below.
Description
Cap
Allen wrench
Hex 1
Refrigerant Piping
Field Supplied
Cap
Refrigerant
To Outdoor Unit
Pressure
Seat Surface
Fully closed position
Check Joint
Only the charging those can be connected
Cap
O-Ring
Rubber
Open – Counterclockwise
Spindle valve
Close – Clockwise
Tighten torque (N.m)
Valve type / Model
A
Liquid Valve: (3~5HP)
7~9
33~42
Gas Valve:
(3~5HP) 11~12
14~18
CAUTION:
− At the test run, fully open the spindle. If not fully
opened, the devices will be damaged.
Description
Insulation Material
Insulation Material
Field Supplied
Insulation Material
Close before shipment
Remaks
Size (mm)
B
C
D
Hex 1
33~42
14~18
4
68~82
8~12
4
6. Multikits and Piping Connection Size of Outdoor Unit &

Indoor Unit..

- Applicable Multikit
Branch Type
Header Type
- Pipe Size

Outdoor Unit

Gas
RAS-3FSVNE
RAS-4FSVNE
∅15.88
RAS-5FSVNE
Indoor Unit
Gas
0.8~1.5 HP
∅12.90
∅15.88
1.8~2.0 HP
∅15.88
2.5~5.0 HP
Code
E-102SN
E-84HSN
E-108HSN
Pipe Size
Liquid
∅9.53
Pipe Size
Liquid
∅6.35
∅6.35
∅9.53

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Ras-4fsvneRas-5fsvne

Inhaltsverzeichnis