Seite 4
Parameterlisten
Istwertliste
Anz Code Bereich / Beschreibung
Fühler 1 ....................................... 1 ...... Anzeigebereich -100/+100°C, Korrekturmöglichkeit hier +/- 10K ........................................Werksabgl.
Fühler 2 ....................................... 1 ...... dto. .......................................................................................................................................Werksabgl.
Fühler 3 ....................................... 1 ...... dto. .......................................................................................................................................Werksabgl.
Fühler 4 ....................................... 1 ...... dto. .......................................................................................................................................Werksabgl.
Fühler 5 ....................................... 1 ...... dto. .......................................................................................................................................Werksabgl.
Fühler 6 ....................................... 1 ...... dto. .......................................................................................................................................Werksabgl.
Fühler 7 ....................................... 1 ...... ±100°C, Virtueller Istwert, gebildet aus Temperatur-Istwerten und eingestellter Gewichtung
Laufz(eit) Kühlung 1 .........X ........ 1 ...... 24:00 h:min maximal ............................................................................................................00:00
bis
Laufz(eit) Kühlung 4 .........X ........ 1 ...... 24:00 h:min maximal ............................................................................................................00:00
Laufzeit Tür 1 ....................X ........ 1 ...... 24:00 h:min maximal ............................................................................................................00:00
bis
Laufzeit Tür 4 ....................X ........ 1 ...... 24:00 h:min maximal ............................................................................................................00:00
Rest Tür auf 1 ...................X ........ 2 ...... h:min:sec ..............................................................................................................................
bis
Rest Tür auf 4 ...................X ........ 2 ...... h:min:sec ..............................................................................................................................
Rest Temp. Warnv. ...........X ........ 2 ...... h:min:sec ..............................................................................................................................
Rest Abtau max. ...............X ........ 2 ...... h:min:sec ..............................................................................................................................
Rest Pause Abt. 1 .............X ........ 2 ...... h:min:sec ..............................................................................................................................
bis
Rest Pause Abt. 4 .............X ........ 2 ...... h:min:sec ..............................................................................................................................
Rest Vent Anlauf 1 ............X ........ 2 ...... h:min:sec ..............................................................................................................................
bis
Rest Vent Anlauf 4 ............X ........ 2 ...... h:min:sec ..............................................................................................................................
Rest Stand Verd. 1 ...........X ........ 2 ...... h:min:sec ..............................................................................................................................
bis
Rest Stand Verd. 4 ...........X ........ 2 ...... h:min:sec ..............................................................................................................................
Restl. Ausl. SI-Ke(tte) .......X ........ 2 ...... h:min:sec
Diff Abt Rest Zeit ...............X ........ 2 ...... min:sec .................................................................................................................................00:00:00
Diff Abt Anf gesp ...............X ........ 2 ...... Ja, Nein ................................................................................................................................Nein
Magnetventil .....................X ........ 2 ...... freigegeben, aus
Betriebszustand ................X ........ 1 ...... Aus Kreisl(auf) X
Tag/Nachtbetrieb ..............X ........ 1 ...... Tag, Nacht
Laufzeit Relais 1 .......................... 2 ...... h:m:s, nur rücksetzbar .........................................................................................................00:00:00
bis
Laufzeit Relais 6 .......................... 2 ...... h:m:s, nur rücksetzbar .........................................................................................................00:00:00
Analogwert........................X ........ 1 ...... Ausgang ist X% des gewählten Ber.
OK1 OK2 OK3 OK4 ..........X ........ 1 ...... Spannung am jeweiligen Eingang
Relaiszustände
X
Sollwertliste
Sollwertebene ................................. 1 .......1, 2 ................................................................................................................................................. 1
Tagsollwert 1 ................................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Tagsollwert 2 ................................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Tagsollwert 3 ................................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Tagsollwert 4 ................................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Nachtsollwert 1 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Nachtsollwert 2 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Nachtsollwert 3 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Nachtsollwert 4 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Tagsollwert 1 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Tagsollwert 2 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Tagsollwert 3 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Tagsollwert 4 ............................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Nachtsollwert 1 ........................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Nachtsollwert 2 ........................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Nachtsollwert 3 ........................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
2. Nachtsollwert 4 ........................... 1 .......-50/+50°C ...................................................................................................................................... -20°C
Warnabstand .................................. 2 .......0...50K, (relativ zum Sollwert) ...................................................................................................... 7 K
2. Warnabstand .............................. 2 .......0...50K, (relativ zum Sollwert) ....................................................................................................... 7 K
Warngrenze unten .......................... 2 .......-50/+50°C (Absolutwert, Wert für Untertemp.-begrenzung und Untertemp.warnung) ............... - 22°C
2. Warngr. unten ............................. 2 .......-50/+50°C (dto.) ............................................................................................................................. - 22°C
Hysterese ........................................ 2 .......0,1...20K ........................................................................................................................................ 2 K
PID Prop.Bereich ............................ 2 .......0,1...30K ........................................................................................................................................ 4 K
PID Nachlaufzeit ............................. 2 .......Aus, 00:00 bis 10:00 min:sec ........................................................................................................ 10 sec.
PID Vorhaltezeit .............................. 2 .......Aus, 00:00 bis 00:10 min:sec ........................................................................................................ Aus
PID Verz. Zeit T1 ............................ 2 .......Aus, 0,1 bis 10 sec. ....................................................................................................................... Aus
Opto->Analogwert .......................... 2 .......0,0...100,0 %, Spannung/Strom am Analogausgang bei aktiviertem OK-Eingang .................... 0%
Ventilatoranlauf ............................... 2 .......0:00:00 bis 0:30:00 (h:min:sec), Anfrierzeit .................................................................................. 0:05:00
Ventilatornachl(auf) ........................ 2 .......00:00 bis 30:00 min:sec ................................................................................................................ 00:00
Temp. Warnverz.............................. 2 .......0:00:00 bis 2:00:00 (h:min:sec) .................................................................................................... 0:45:00
Grenzlaufz.Kühl .............................. 2 .......0:00 bis 23:59 (h:min), Aus ........................................................................................................... Aus
Grenzlaufz.Tür ................................ 2 .......0:00 bis 23:59 (h:min), Aus ........................................................................................................... Aus
Verz.Kühl.n.Netz ............................. 2 .......0...30 min ....................................................................................................................................... 0 min
Mindestst. Verd. .............................. 2 .......00:00 bis 30:00 hh:mm ................................................................................................................. 00:00
Opto.-Warnverz. ............................. 2 .......00:00 bis 02:00 hh:mm ................................................................................................................. 00:05
Warnverz. Tür ................................. 2 .......00:01 bis 04:00 hh:mm ................................................................................................................. 00:05
Ausl. Zeit Si-Ke(tte) ......................... 2 .......00:00 bis 01:00 min:sec ................................................................................................................ 01:00
Parameter, die mit "nur Anz." gekennzeichnet sind, dienen nur der Information
und können nicht verändert werden.
Funktionen dieses Fühlers:
Rx = Regelfühler x, Wx = Warnfühler x, An = Anzeigefühler, wx = Bed.Abt.Fühl warm x,
kx = Bed Abt Fühl kalt x, Axx = Abtaufühler Kreis x / Nr.x
1
Zustand Relais 1-6, 1=ein, 0=aus ........................................................................................ein = angezogen,
Code Bereich
Untertemperaturbegrenzung ist nicht abschaltbar.
Betriebsanleitung Kühlstellen-Prozessoren TKP / TKC x130 - x140
Die Nummern in der Spalte "Code" bezeichnen die Bedienerebene, in der
diese Parameter sichtbar sein können.
Werkseinstellung
aus = abgefallen
Werkseinstellung