CHAPTER 4 - KEYPAD (HMI) OPERATION
Programming Error – E24
P265 = 3 and other(s) D I(s)  Start-Stop or FWD and REV or ON and OFF
P266 = 3 and other(s) D I(s)  Start-Stop or FWD and REV or ON and OFF
JOG
P267 = 3 and other(s) D I(s)  Start-Stop or FWD and REV or ON and OFF
P268 = 3 and other(s) D I(s)  Start-Stop or FWD and REV or ON and OFF
Two or more parameters between P264, P265, P266, P267 and P268 equal to 1
Local/Remote
(LOC/R EM)
Disables Flying
P265 = 13 and P266 = 13 or P267 = 13 or P268 = 13
Start
Reset
P265 = 10 and P266 = 10 or P267 = 10 or P268 = 10
P263 = 14 and P264  14 or P263  14 and P264 = 14
On/Off
Direc tion of
Two or more parameters P264, P265, P266, P267 and P268 = 0 (Direction of Rotation)
Rotation
P263 = 8 and P264  8 and P264  13
P263 = 13 and P264  8 and P264  13
P263  8 and P263  13 and P264 = 8
FWD/REV
P263 = 8 or 13 and P264 = 8 or 13 and P265 = 0 or P266 = 0 or P267 = 0 or P268 = 0
P263 = 8 or 13 and P264 = 8 or 13 and P231  2
P221 = 6 or P222 = 6 and P264  7 and P265  7 and P266  7 and P267  7 and P268  7
Multispeed
P221  6 and P222  6 and P264 = 7 or P265 = 7 or P266 = 7 or P267 = 7 and P268 = 7
P221 = 4 or P222 = 4 and P265  5 or 16 and P266  5 or 16 and P267  5 or 16 and
P268  5 or 16
P221  4 or P222  4 and P265 = 5 or 16 or P266 = 5 or 16 or P267 = 5 or 16 or
Electronic
P268 = 5 or 16
P265 = 5 or 16 and P266  5 or 16 and P268  5 or 16
Potentiometer
P266 = 5 or 16 and P265  5 or 16 and P267  5 or 16
P267 = 5 or 16 and P266  5 or 16 and P268  5 or 16
P268 = 5 or 16 and P265  5 or 16 and P267  5 or 16
Rated Current
P295 incompatible with the inverter model
DC Braking and
P300  0 and P310 = 2 or 3
Ride-through
PID
P203 = 1 and P221 = 1,4,5,6,7 or 8 or P222 = 1,4,5,6,7 or 8
P265 = 6 and P266 = 6 or P265 = 6 and P267 = 6 or P265 = 6 and P268 = 6
P266 = 6 and P267 = 6 or P267 = 6 and P268 = 6 or P266 = 6 and P268 = 6
P265 = 6 or P266 = 6 or P267 = 6 or P268 = 6 and P263 = 13
Ramp 2
P265 = 6 or P266 = 6 or P267 = 6 or P268 = 6 and P264 = 13
P265 = 6 or P266 = 6 or P267 = 6 or P268 = 6 and P263 = 13
P265 = 6 or P266 = 6 or P267 = 6 or P268 = 6 and P264 = 13
P221 = 2,3,7 or 8 and standard inverter
Model
P221 = 2,3,7 or 8 and standard inverter
P221 = 1 or P222 = 1 and P235 = 2, 3, 4 or 5
Analog Input
P221 or P222 = 2 or 3 and P239 = 2, 3, 4 or 5
72
Table 4.1 - Incompatibility of parameters - E24
NOTE!
It is possible that during programming occurs the error E24
caused by incompatibility between some parameters already
programmed.
In this case do not stop with the parameter setting. If at the
end of the parameter setting does not disappear, check the
table of incompatibilities (table 4.1).