Figure 3.10 - Jumpers position for selecting the analog inputs and outputs operation mode (voltage - 0 to 10 Vdc
or current - 0 to 20 mA / 4 to 20 mA) as well as the digital inputs operation mode (high logic level - PNP or low
logic level - NPN). Refer to the digital inputs definition on items 3.2.5.1 and 3.2.5.2
I/O
DI1 to DI4
Refer to the parameters P263,
P264, P265 and P266
AO
Output Frequency
AI1
Frequency / Speed Reference
(remote mode)
AI2
No Function
CHAPTER 3 - INSTALLATION AND CONNECTION
DI
A O
AI1
AI2
As a default, the analog inputs and outputs are set to voltage
mode (0 to 10) Vdc and the digital inputs are set to active
(NPN logic). Change it by using DIP switch S1 (refer to figure
3.10) on the control board and by setting parameters P235,
P239 and P253 (refer to table 3.6).
Factory Default Setting
Table 3.6 - Dip switch configuration (inputs and outputs)
NOTE!
If it's used a (4 to 20) mA signal, set parameter P235, P239
and P253 that defines the signal type at AI1, AI2 and AO
respectively.
The parameters related to the analog inputs are: P221,
P222, P234, P235, P236, P238, P239, P240, P251, P252,
P253.
DIP
Switch
S1:1
OFF: digital inputs as low active (NPN)
ON: digital inputs as high active (PNP)
S1:2
ON: (0 to 10) Vdc
OFF: (4 to 20) mA or (0 to 20) mA
S1:3
OFF: (0 to 10) Vdc or DI5
ON: (4 to 20) mA or (0 to 20) mA or PTC
S1:4
OFF: (0 to 10) Vdc or DI6
ON: (4 to 20) mA or (0 to 20) mA or PTC
Selection
43