3.2.6 Typical Terminal
Connections
S1: FWD/REV
S2: Reset
S3: Start/Stop
R1: Potentiometer for
speed setting
CHAPTER 3 - INSTALLATION AND CONNECTION
NOTES!
The inverter is factory default programmed with the digital
inputs as low level active (S1:1 in OFF). When the digital
inputs are used as high level active, you must set the jumper
S1:1 to ON.
The jumper S1:1 selects the high level or low level active
for all 4 digital inputs. You can not select them separately.
Connection 1 - Keypad Start/Stop (local mode)
With the factory default programming, you can operate the
inverter in local mode with the minimum connections shown in
figure 3.6 (Power) and without control connections. This
operation mode is recommended for users who are operating
the inverter for the first time. Note that there is no need of
connection of control terminals.
For start-up according to this operation mode, refer to chapter 5.
Connection 2 - Wire Start/Stop (remote mode)
Valid for factory default programming and inverter operating
in remote mode. For the factory default programming, the
selection of the operation mode (local/remote) is made via
the key
(default is local).
The figure 3.16 shows the inverter terminal connection for this
type of driving.
1
2
3
S3
S1
S2
Figure 3.16 - XC1 wiring for connection 2
4
5
6
7
8
R1
5k
9
10
11
12
47