ACTION
Use the
and
to select the control type
Press
to save the selected
option and to start the tuning routine
after changing to Vector Control mode
Press the
key and use the
keys
and
to set the
correct rated motor efficiency (in
this case 71 %)
Press the
key to save the
selected option and to exit the
programming mode
Press the
key to go to the
next parameter
Press the
key and use the
keys
and
to set the
correct rated motor voltage
Press the
key to save the
selected option and to exit the
programming mode
Press the
key to go to the
next parameter
Press the
key and use the
keys
and
to set the
correct rated motor current (in this
case 2.90 A)
Press
key to save the
selected option and to exit the
programming mode
Press the
to go to the next
parameter
Press the
key and use the
keys
and
to set the
correct motor speed (in this case
1720 rpm)
Press the
key to save the
selected option and exit the
programming mode
Press the
key to go to the
next parameter
HMI DISPLAY
keys
CAPITOLO 4 - START
DESCRIPTION
P202 = 2: Vector
Motor efficiency:
50 to 99.9 %
Set motor efficiency:
71 %
Exit the programming mode
Rated motor voltage range:
0 to 600 V
Set rated motor voltage:
220 V (the default value is maintained)
Exit the programming mode
Rated motor current range:
0.3 x I
to 1.3 x I
nom
nom
Set rated motor current: 2.90 A
Exit the programming mode
Rated motor rpm range:
0 to 9999 rpm
Programmed rated motor rpm:
1720 rpm
Exit the programming mode
Rated motor frequency:
0 to F
max
(2)