3.2.5 Signal and Control
Connections
CCW
CW
Factory Default
Settings
Figure 3.8 - XC1 control terminal description (standard control board - CFW-08)
CHAPTER 3 - INSTALLATION AND CONNECTION
The signal connections (analog inputs/outputs) and control
connections (digital inputs and relay outputs) are made on
the XC1 connector of control board (refer to the location in
figure 3.5, item 3.2.2).
There are two configurations for the control board: standard
version (CFW-08 line) and Plus version (CFW-08 Plus line),
as shown below:
XC1 Terminal
Factory Default Function
Digital Input 1
1
DI1
General Enable
Digital Input 2
2
DI2
FWD / REV
Digital Input 3
3
DI3
Reset
Digital Input 4
4
DI4
Start/Stop
5
GND
0 V Reference
Analog Input 1 or Digital Input 5
or PTC Input
AI1 or
6
DI5 or
Frequency / Speed Reference
PTC1
(remote mode)
7
+10 V
Potentiometer Reference
8
GND
0 V Reference
9
Not Used
Relay Output 1 - N.C. Contact
10
N.C.
No Fault (P277 = 7)
11
Commom
Relay 1 Common Point
Relay 1 - N.O. Contact
12
N.O.
No Fault (P277 = 7)
Note: NC = Normally Closed Contact, NO = Normally Open Contact.
Description
4 isolates digital inputs
- Logic NPN
Minimum high level: 10 Vdc
Maximum high level: 30 Vdc
Maximum low level: 3 Vdc
- Logic PNP
Maximum low level: 10 Vdc
Minimum high level: 21.5 Vdc
Maximum high level: 30 Vdc
Input current: -11 mA
Maximum input current: -20 mA
Not connected to PE
( 0 to10) Vdc (0 to 20) mA (4 to 20)
mA (figure 3.10)
Impedance: 100 k (voltage input)
and 500  (current input).
- Linearity error < 0,25 %
- Maximum voltage input: 30 Vdc
For further information refer to P235
detailed parameter description
+10 Vdc, ± 5 %, capacity: 2 mA
Relay 1
Contact capacity:
0.5 A / 250 Vac
Specifications
10
12
11
41