EFC x610 Series
Digital output DO1a, DO1b load pull-up / pull-down wiring
①
Load pull-up wiring with internal power
supply
②
Load pull-down wiring with internal
power supply
Fig. 8-11: Digital output DO1a, DO1b load pull-up / pull-down wiring
For internal supply, ONLY USE terminal +24 V and NEVER USE terminal +10 V
●
or +5 V!
For external supply, its reference ground MUST be connected to terminal
●
COM!
DOK-RCON03-EFC-X610***-IT06-EN-P
Frequency Converter Wiring
③
Load pull-up wiring with external power
supply
④
Load pull-down wiring with external
power supply
Bosch Rexroth AG
65/421