Communication

14.3.4 Communication Mapping Register Address Distribution

Frequency converter parameter address

Frequency converter parameter registers correspond to the function codes one-
to-one. Reading and writing of related function codes can be achieved through
reading and writing of the contents in frequency converter parameter registers
via Modbus communication. The characteristics and scope of reading and writ-
ing function codes are in compliance with the frequency converter function code
description. The address of a frequency converter parameter register is com-
posed of a higher byte representing the function code group and a lower byte
representing the index in the group. The groups are mapped as follows:
Address
0x00
high byte
Group
b0
Address
0x35
high byte
Group
E5
Tab. 14-22: Frequency converter parameter registers
Parameters of the monitoring group (Group d0) are always write-pro-
tected.
Examples:
To read out the module temperature (d0.20) of EFC x610 frequency converter,
use register address 0x1014 (0x10 = Group d0, index 0x14 = 20).
To set V/f curve mode (C2.00) of EFC x610 frequency converter, use register ad-
dress 0x2200 (0x22 = Group C2, index 0).
Access to a non-existing function code will be acknowledged with exception
code 3 (see
chapter 14.3.3 "Modbus Function and Message Format" on page
274).
282/421
0x20
0x21
0x22
C0
C1
C2
0x38
0x39
0x60
E8
E9
H0
0x23
0x30
0x31
C3
E0
E1
0x61
0x68
0x69
H1
H8
H9
DOK-RCON03-EFC-X610***-IT06-EN-P
EFC x610 Series
0x32
0x33
0x34
E2
E3
E4
0x40
0x41
0x10
U0
U1
d0

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis