Diagnosis
13.4.25 Error 39 (EPS-): DC_IN Power Supply Error
Possible reason
DC_IN power supply voltage is out of
range 20...28 V
13.4.26 Error 40 (dir1): Forward Running Lock Error
Possible reason
Direction control [E0.17] = '1: Forward
only'
Direction command is reverse
13.4.27 Error 41 (dir2): Reverse Running Lock Error
Possible reason
Direction control [E0.17] = '2: Reverse
only'
Direction command is forward
13.4.28 Error 42 (E-St): Terminal Error Signal
Possible reason
External error caused by input signals via
external terminals
Wrong wiring / setting of multi-function
external terminals
Converter stop caused by E-Stop active
command via Modbus communication
13.4.29 Error 43 (FFE-): Firmware Version Mismatch
Possible reason
Operating panel may be placed to the frequency converter
with older/newer firmware
Control board may be removed to another device
Extension card may be installed to the frequency converter
with older/newer firmware
262/421
Solution
Check the voltage supply on DC_IN terminal and make sure
the voltage is within the range of 20...28 V
Solution
Correct the parameter setting
Solution
Correct the parameter setting
Solution
Check external terminals status
Ensure the right external signals have been connected cor-
rectly to the right multi-function external terminals which
are assigned for external error input ([E1.00]...[E1.04] =
32, 33)
Check the stop command via Modbus communication
(0X0088: stop according to parameter setting; 0X0090:
E-stop active). If converter receives 0X0090 , E-St will be
displayed
Solution
Contact with service
Contact with service
Contact with service