Herunterladen Inhalt Inhalt Diese Seite drucken

Stop And Pause Simple Plc Control - REXROTH EFC 5610 serie Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Bosch Rexroth AG
Functions and Parameters

12.8.4 Stop and Pause Simple PLC Control

Active 'Simple PLC control' can be stopped or paused by configuration of digital
inputs with functions of 'Simple PLC stop' or 'Simple PLC pause'.
Code
Name
E1.00
X1 input
E1.01
X2 input
E1.02
X3 input
E1.03
X4 input
E1.04
X5 input
H8.00
EX1 input
H8.01
EX2 input
H8.02
EX3 input
H8.03
EX4 input
26: Simple PLC stop
The frequency converter stops output till next 'Run command' is active, and
the motor freewheels to stop.
27: Simple PLC pause
'PLC control' is paused and the frequency converter decelerates to run at 0
Hz till the pause signal is inactive.
A typical simple PLC pause process is as listed in the table below:
Simple PLC
Step
pause
1
Inactive
2
Active
3
Inactive
4
Inactive
5
Inactive
Tab. 12-17: Typical simple PLC pause process
194/421
26: Simple PLC stop
27: Simple PLC pause
Run command
Converter status
Active
Run
Decelerating to 0 Hz
Active
(No stop DC-braking)
Accelerate to
Active
previous stage
Inactive
Stop
Active
Run
Setting range
Description
Simple PLC cycles with
each stage
Dec. time is according
to current simple PLC
stage setting
Acc. Time is according to
previous simple PLC stage
setting before pause
Stop according to [E0.50]
Restart from 1
simple PLC stage
DOK-RCON03-EFC-X610***-IT06-EN-P
EFC x610 Series
Default
Min.
Attri.
35
Stop
36
Stop
0
Stop
0
Stop
0
Stop
0
Stop
0
Stop
0
Stop
0
Stop
st

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis