EFC x610 Series
12.5.3 Direction Control
Direction control via operation panel
The actual direction is controlled by the configuration of parameter [U0.00] 'Di-
rection control by panel' and [E0.17] 'Direction control'.
Code
Name
Direction
control
U0.00
panel
E0.17 Direction control
[E0.17] setting
0
Forward / Reverse
1
Forward only
2
Reverse only
3
Swap default direction
Tab. 12-9: Direction configuration
For error codes 'dir1', 'dir2' concerning direction control, see
ter 13.4 "Error Code" on page
Reverse running frequency
Code
Name
E0.11
Reverse running frequency
When the converter is running in reverse direction, the setting frequency will be
defined by E0.11.
This reverse running frequency is ONLY active when converter is NOT
running in multi-speed, simple PLC, or PID control mode.
DOK-RCON03-EFC-X610***-IT06-EN-P
Setting range
0: Forward
by
1: Reverse
0: Forward / Reverse
1: Forward only
2: Reverse only
3: Swap default direction
[U0.00] setting
Forward
Reverse
Forward
Reverse
Forward
Reverse
Forward
Reverse
256.
Setting range
0.00...[E0.09] Hz
Bosch Rexroth AG
Functions and Parameters
Default
0
0
Actual direction
Forward
Reverse
Forward
Converter stop and show error code 'dir1'
Converter stop and show error code 'dir2'
Reverse
Reverse
Forward
Default
0.00
Min.
Attri.
–
Run
–
Stop
chap-
Min.
Attri.
0.01
Run
163/421