Herunterladen Diese Seite drucken

Brine Controller; Remote Control; Building Management Technology; Smart Rtc - Dimplex SIW 6 TU Montageanleitung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4.2 Brine controller

If required by the authorities, the brine controller must be incor-
porated in the heat source main line (brine accessories package)
as follows.

4.3 Remote control

A remote control adds convenience and is available as a special
accessory. Operation and menu navigation are identical to those
of the heat pump manager. Connection is made using a 6-core
telephone cable (special accessory) with modular plugs.
NOTE
In the case of heating controllers with a removable operating element,
this can also be used directly as a remote control.
4.4 Building management
technology
The heat pump manager can be connected to a building man-
agement system network via supplementation of the relevant ex-
tension. The supplementary installation instructions of the exten-
sion must be consulted regarding the exact connection and
parameterisation of the interface.
The following connections can be made on the heat pump
manager:
Modbus
EIB, KNX
Ethernet
ATTENTION!
If the heat pump or circulating pumps are controlled externally, an
additional flow rate switch is required to prevent the compressor from
being switched on when there is no volume flow.
www.dimplex.de

4.5 Smart RTC

The Smart RTC is a room temperature controller with a display,
which is used both to display the current room temperature and
to set the desired room temperature. It is available in a surface-
mounted version (RT Econ A) and a flush-mounted version (RT
Econ U). Temperature sensors for measuring the room tem-
perature are already integrated into both versions.
The supplementary installation instructions of the Smart RTC
must be consulted regarding its installation and operation.
5

Transport

5.1 General

A lift truck is suited for transporting the unit on a level surface.
Carrying straps may be used if the heat pump needs to be trans-
ported on an uneven surface or carried up or down stairs. These
straps can be passed directly underneath the pallet.
ATTENTION!
In installed and dismantled state, the heat pump module may only be
tilted by a maximum of 45° (in each direction).
452236.66.01 · FD 9206
SIW 6TU - SIW 11TU
EN-5

Werbung

loading

Diese Anleitung auch für:

Siw 11tuSiw 8tu