Very early fire detection / fire extinction
Component
Function
A30:2
Goes off in case of smoke, from
pre-alarm
light diffusion of 60% of the main
alarm value
(alarm = 1)
is signaled:
Web visualisation
SNMP trap
A30:4
Goes off when smoke occurs,
main alarm
from 0.5% of light diffusion/m
(alarm = 1)
is signaled:
Web visualisation
SNMP trap
A30:32
Internal defect of very early fire
disturbance
detection
(alarm = 0)
is signaled:
Web visualisation
SNMP trap
Extinction triggered
When fire extinction is installed,
report when extinction has been
triggered
(message = 1)
is signaled:
Web visualisation
SNMP trap
Heat flowmeter
Component
Function
B11
Temperature measurement
temperature chilled
water feed
is signaled:
Web visualisation
display
SNMP
B12
Temperature measurement
temperature chilled
water return
is signaled:
Web visualisation
display
SNMP
B26
Measurement of water flow
Flowmeter
is signaled:
Web visualisation
display
SNMP
CoolTherm
Assembly Connection Variables
5-DI4:1
31.1.1
5-DI4:2
32.2.1
5-DI4:3
31.1.4
5-DI4:4
32.2.4
Assembly Connection Variables
2-
49.1.1
2RTD:Ch
49.1.2
1
2-
50.2.1
2RTD:Ch
50.2.2
2
2-AI2:Ch 1 51.1.2
51.1.3
01_998_330_0_m
SNMP
rauch_valm
Status check
Trap in case of
status change
rauch_halm
Status check
Trap in case of
status change
rauch_fail
Status check
Trap in case of
status change
rauch_glt
Status check
Trap in case of
status change
SNMP
was_klt_in
Value requested
Trap in the event
of falling short of
or exceeding limit
values
was_wrm_in
Value requested
Trap in the event
of falling short of
or exceeding limit
values
was_flow_in
Value requested
page / Seite 76/157