Herunterladen Inhalt Inhalt Diese Seite drucken

Operating Conditions - Knurr CoolTherm Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für CoolTherm:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CoolTherm
Manual / Bedienungsanleitung
2.

Operating conditions

Correct use
The unit is a server cabinet cooling device and is only used for the
removal of heat from server cabinets to protect temperature
sensitive components. The cooling system in the cabinet is thermally
independent of the room air. Total heat load of the installed equipment is
taken out of the room using the chilled water circuit. Note: Under special conditions a very
small amount can dissipate to the room (approx. 05, kW)
For reliable function of the CoolTherm, chilled water
must be available in the correct amount, and at the correct
temperature and pressure. Observe water quality as per
VGB-R 455 P. (see Appendix)
Ambient temperature:
Absolute humidity in the installation location:
Water temperature, feed:
Water temperature, return:
Temperature spread, water:
Use of anti-freeze in the chilled water:
Water connection:
Condensed water connection:
Nominal voltage at cooling capacity:
12 KW, 17 KW, 25 KW
Voltage rating for US
Max. operating pressure:
CoolTherm
10°C / 50°F to 35°C / 95°F
(other temperatures upon request)
Temperatures on use of RMS with
temperature-dependent alarm:
20°C / 68°F to 25°C / 77°F
8 g H
12°C / 53°F
(other temperatures upon request)
18°C / 64.4°F
(other temperatures upon request)
6K
upon request
from below
from below
200V to 264V /
50Hz / 60 Hz
196 - 253 V AC for 50 Hz
217 - 264 V AC for 60 Hz
all MCB double-pole for US
10 bar / 145 PSI
01_998_330_0_m
O/ kg air maximum
2
page / Seite 6/157

Werbung

Kapitel

Inhaltsverzeichnis
loading

Verwandte Produkte für Knurr CoolTherm

Inhaltsverzeichnis