The suck in of air with water droplets can also be prevented (Door opening due to humidity alarm).
When the rear door is opened, the fans will be shut down.
In case of fire and smoke development in the rack the doors are kept closed and the fans will be
shut down. The door opening due to overtemperature will be suppressed.
Alternative the consciously opening of the doors is possible to extinguish the fire by a room
extinguishing device.
It is possible that every time the doors could open themself.
Mind this during staying in door area.
Release of Automatic Door Opening
- via temperature sensor front side (standard)
- optional via smoke detector
- optional via RMS (Rack Monitoring System) coupled signal
overtemperature
humidity report
or
separate thermostat