Herunterladen Inhalt Inhalt Diese Seite drucken

Storage And Transportation - Knurr CoolTherm Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für CoolTherm:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CoolTherm
Manual / Bedienungsanleitung
figure optional three - way valve control characteristic (factory setting)
4.

Storage and transportation

Cover open pallets with tarpaulins and protect the components
from soiling (e. g. sand, rain, dust, etc.).
Keep storage temperatures between –30 °C and +50 °C / -22°F and 104°F.
The heat exchanger must be completely drained (to prevent the risk of
frost damage)
When stored for more than 1 year, check the the fan bearings prior to
installation. (⇒ Turn fans by hand.)
CoolTherm can be transported using a forklift truck or crane. For transport
using a crane, straps must be used. The CoolTherm weighs, depending on
the version, up to 340 kg / 749 lbs. (net weight)
Avoid twisting the housing or other damage.
Use suitable tools during installation, e. g. approved scaffolding.
Prior to lifting the CoolTherm using a crane or forklift truck, close all doors.
Do not stand under suspended loads.
Hooks attached to the load must be be of appropriate tensile strength.
CoolTherm must not be lifted at an angle using a crane.
All packaging is to be removed prior to commissioning CoolTherm.
CoolTherm
Start at 16°C
air inlet
temperature
01_998_330_0_m