Herunterladen Inhalt Inhalt Diese Seite drucken

Knurr CoolTherm Bedienungsanleitung Seite 70

Vorschau ausblenden Andere Handbücher für CoolTherm:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

CoolTherm
Manual / Bedienungsanleitung
Functionality of the Basic Variant
Component
Function
Fan 1
Status fan 1
(Alarm. = 0)
Failure is signaled:
Web visualisation
display
flashing light
SNMP trap
Fan 2
Status fan 2
(Alarm. = 0)
Failure is signaled:
Web visualisation
display
flashing light
SNMP trap
Fan 3
Status fan 3
(Alarm. = 0)
Failure is signaled:
Web visualisation
display
flashing light
SNMP trap
S11 –
Status door, rear CoolTherm /
contact switches
-Therm
CoolTherm /-
Therm, rear
signaling:
(door closed = 1)
Web visualisation
display (optional)
flashing light (optional)
relay contact (optional)
B8 -
Message when water level in
water sensor
condensate collection tub
high
(Alarm = 1)
is signaled:
Web visualisation
display
flashing light
SNMP trap
B7 -
Signaling smoke; if required,
smoke sensor
doors can be opened and
server shut down
(Alarm = 1)
(optional)
is signaled:
Web visualisation
display
flashing light
SNMP trap
Q12 -
Mains supply failed
Mains contactor
mains A
is signaled:
Web visualisation
(Mains A avail. =
display
1)
flashing light
SNMP trap
K15 -
Standby net failed
Monitoring mains
B
is signaled:
Web visualisation
CoolTherm
Assembly
Connection
ILC150:I1
5.1.1
ILC150:I2
6.2.1
ILC150:I3
5.1.4
ILC150:I4
6.2.4
ILC150:I5
7.3.1
ILC150:I6
8.4.1
ILC150:I7
7.3.4
ILC150:I8
8.4.4
01_998_330_0_m
Variables
SNMP
ONBOARD_
Status check
INPUT_BIT0
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT1
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT2
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT3
Trap in case of
tuer_c_h
status change
ONBOARD_
Status check
INPUT_BIT4
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT5
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT6
Trap in case of
status change
ONBOARD_
Status check
INPUT_BIT7
Trap in case of
status change