6
Installation
6.1
Safety information
›
Mounting may only be carried out by trained, qualified personnel.
›
Comply with the system-related conditions and the requirements of the system manufacturer or plant builder.
›
Safety components, e.g. protective grids, may not be dismantled or circumvented or put out of function.
WARNING
Danger of impact from fan or parts of fans dropping!
»
Check the base before installation for load capacity/strength.
»
When selecting the hoisting device and fitting material observe the weight, tendency to vibrations and shear
forces (weight information on the name plate).
»
Wear helmet and protective goggles.
6.2
Preconditions for installation
•
Place of installation protected against dust.
•
The base or the roof fan must have been integrated into the roof waterproofing.
•
For roof inclinations >5° an inclined roof base must be used.
•
The minimum distance between the fans if a number of fans are being assembled is 1x rotor diameter.
6.3
Assembly information
WARNING
Risk of crushing in hinged fans by the hinged frame shutting!
›
The hinged frame is very heavy because the fan wheel has been fitted on it.
›
Open and close the hinged frame carefully
In installation, do not distort the fan housing.
"
Install the fan such that no vibrations are transmitted to the channel system of the housing frame.
"
Pay attention to the direction of flow (arrows).
"
Provide for contact and intake protection and safety distances according to DIN EN 294 and DIN 24167-1.
"
Ensure uninhibited and constant inflow into the appliance and free blow-out.
"
Ensure that the fan is installed firmly and stably.
"
6.3.1
Assembly
Examples of assembly can be found in the Description chapter.
Ensure secure access to the fan for maintenance and service.
"
Assemble the base frame on a level, flat base (see prerequisites for assembly).
"
Assemble the fan at the corners of the base by means of 4 screws.
"
Seal the contact surface between the base frame and the base with cellular rubber or a foamed band.
"
Install connecting ducts and accessories.
"
Provide for contact/intake protection and safety distances according to EN ISO 13857.
"
NOTE
In some cases it is better to mount accessories before placing the fan on the roof base.
Installation