3.3

Transportation and storage

All fans are packaged at the factory to withstand normal transport handling. When handling the goods use suitable lift-
ing equipment in order to avoid damage to fans and personnel. Avoid blows and shock loads. Store the fans in a dry
place protected from weather and dirt until final installation.
Warning
• The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use
protective clothing.
• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.
4
Installation
Danger
• Make sure that the mains supply to the unit is disconnected before performing any maintenance or
electrical work!
• All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
Warning
• The units electrical connection to the mains supply must be preceded by an all pole circuit breaker with a
minimum 3 mm gap.
• Do not lift the fans by the connecting cable, connection box, motor bracket, impeller or inlet cone.
• The fans are not to be used in hazardous environments or connected to flue ducts.
• The appliance must be connected to a mains circuit breaker in the fixed installation.
Caution
• Make sure protection grid has been installed (EN ISO 13857), no moving parts shall be accessible after
installation.
• Do not remove, short-circuit or disconnect safety accessories (i.e. motor protection, safety grille).
4.1

Installing the fans

1 Install four mounting brackets (pos. 1) to dedicated
positions on the sides of fan housing. Use included
screws (pos. 2). This step can be skipped in case
mounting brackets will not be used for installation.
Stick the enclosed self adhesive anti-vibration rubbers
on the cupboard fan.
GB
211877 | A006