Process calibration 0% and 100% or only 0%

(not for RTD and TC input)
When the option "0% and 100% calibration" is actively configured in PReset it
is possible to make the following process calibrations. Please note: Input 0%
and 100% should be chosen higher than the process-calibrated span.
Process calibration 0% and 100%
1. Apply the actual 0% value.
2. Open the front cover, activate sw. 1 and wait
until the green LED lights constantly.
3. Apply the actual 100% value.
4. Activate sw. 1. The LED will start flashing again.
The input on PRetrans 5116 has now been scaled according to the actual
process values.
When the option "0% calibration" is actively configured in PReset it is possible
to make the following process calibration.
0% process calibration
1. Apply the actual 0% value.
2. Open the front cover and activate sw. 1.
The input on PRetrans 5116 has now been scaled according to the actual
process values.