Parameter
Type
Relay units for
Relay 1 and Relay 2
Setpoint
Setpiont LOW
(setpoint window only)
Setpoint HIGH
(setpoint window only)
Hysteresis
On-delay
Off-delay
Action
Contact
Sensor error
detection
42
Configuration of relay 1 & 2 in PReset
value
Off
Setpoint
Setpoint window
Sensor error indication
Power indication
% of input span
Input units
% of output span
Output units
From min. to max. of relay units
From min. to max. of relay units
From min. to max. of relay units
From 0.1...99.9% of relay units
0..3600 s
0..3600 s
Increasing
Decreasing
Normally open (N.O.)
Normally closed (N.C.)
Open inside window
Closed inside window
Contact open
Contact closed
Hold
Off
Description
No relay function
Relay changes state at a limit
on the span
Relay changes state inside a
range of the span
Only works for sensor error
Relay is active when power
is on
0...100% of input span
E.g. °C, mV and mA
0...100% of output span
mA and V
Setpoint limit
Lower setpoint in setpoint
window
Higher setpoint in setpoint
window
Difference between setpoint
value and reset value. At set-
point window the hysteresis
is outside the window.
Time from the signal crosses
the setpoint threshold until
the relay activates. Time is
reset at setpoint crossing.
Time from the signal crosses
the hysteresis threshold until
the relay deactivates. Time is
reset at hysteresis crossing.
Activates at increasing signal
Activates at decreasing signal
Contact state before limit is
reached
Contact state before limit is
reached
Relay deactivated inside set-
point window
Relay activated inside set-
point window
Relay deactivated
Relay activated
Relay state as before sensor
error occurred
No relay function