Herunterladen Inhalt Inhalt Diese Seite drucken

Automatically Setting The Upper End Point And; Manually Setting The Lower End Point - RADEMACHER 2740 06 65 Original Montageanleitung Und Betriebsanleitung

Duofern-rohrmotoren
Vorschau ausblenden Andere Handbücher für 2740 06 65:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Automatically setting the upper end point and manually setting the lower end point
1.
or
2.
or
SET
3.
4.
5.
6.
7.
or
Symbols and actions when connecting a cord circuit setting unit (22)
or
when connecting an external switch.
Switch on the mains power.
ON
The roller shutters will first travel to the upper stop until the tubular motor switches off automatically.
If the tubular motor is already logged on to the DuoFern network, then the direction of travel can also be specified with DuoFern transmitters.
IMPORTANT
◆ Never interrupt the sequence while the process is running. The roller shutters must be allowed to travel up without interruption.
◆ First move the roller shutters upwards. If the roller shutters first move downwards, then the direction of travel must first be reversed by
pressing the SET button several times or by using the external switch.
◆ The switching sequence for the SET button or the external switch is: OPEN/STOP/CLOSE/STOP, and so on.
Afterwards, the tubular motor will reverse and the roller shutters will move downwards.
Press and hold the set button (11) until the upper end point is reached.
Release the set button (11) as soon as the roller shutters have reached the desired position.
The motor stops and the lower end point is stored.
NOTE
These methods are useful if you want to leave the ventilation slats between the roller shutter lamella open.
You can correct the lower end point in small steps by briefly pressing the set button (11)
IMPORTANT
In the event that a malfunction occurs during configuration, e.g. in the event that the tubular motor only runs for a single rotation even when
the set button is pressed, it is unlikely that the tubular motor is faulty. Possibly the adapter (10) has slipped off of the motor head.
Check and, if necessary, correct the positioning of the adapter (10), see pages 37 and 51.
NOTE
In the event that the end point configuration fails, you must reset the tubular motor to the factory setting (see page 50), in order to repeat
the process.
To conclude the process, disconnect the tubular motor from the power for a few seconds (e.g. by switching the cord circuit
OFF
setting unit (22) toggle switch back to the central position). Subsequently, the tubular motor is ready for operation.
IMPORTANT
◆ If the "external switch" (h) lead is not used, then it must be connected to the neutral conductor (f) (see fig. k).
EN
47

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis