Keep the air and creep distances between intrinsically safe segments!
The maximum current available from the 750-606 or 750-625/000-001 Ex-i
Supply Module is 1 A.
If the use of further DC 24 V Ex i Supply modules is necessary for reasons of
extent of utilization, four Separation Modules (750-616) must be used to
guarantee the distance between the intrinsically safe segments.
Pos : 18.1.17 /Serie 750 ( WAGO-I/O- SYST EM)/Wic htig e Erl äuter ung en/Sic her hei ts- und s onstige Hi nweise/Hinweis/Hi nweis : Potential einspeis eklemme für Erde eins etz en! @ 3\mod_1226499037468_21.doc x @ 25023 @ @ 1
Use potential feed module for Ground (earth)!
The I/O module has no power contacts for PE intake and transfer. Use a potential
feed module when a PE feed is needed for the subsequent I/O modules.
Pos : 18.1.18 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Versorgung/Gal vanisc he Trennung F eld/Sys tem @ 3\mod_1233756478750_21.doc x @ 27102 @ @ 1
The field voltage and the system voltage are electrically isolated from each other.