Displays / Error Messages
Measurement function
Mains internal resistance,
Loop resistance,
RCD test
Mains internal
resistance,
Loop resistance,
RCD Test
Mains internal
resistance,
Loop resistance,
RCD test
Mains internal
resistance,
Loop resistance,
RCD test
Mains internal
resistance,
Loop resistance,
RCD test
Loop Resistance
Mains internal resistance
RCD test
Loop resistance,
Circuit breaker.
RCD test
RCD test
32
Display
Comment/Remark
Contact electrode PE (21) is touched:
PE error, PE not connected.
The phase present at test leads L/L1 or N/L2
Contact electrode PE (21) is touched:
PE error, PE carries a dangerous voltage.
Socket L/L1-N/L2 of test leads or mains plug are trans
posed. Turn shockproof plug.
For exact evaluation touch contact electrode (21)!
Socket error:
A contact voltage exceeding 25 V is present between N
and PE. It is possible that
the impedance of N and/or PE is too high. For exact eval-
uation touch contact electrode (21)!
Socket error:
The voltage between measurement socket L and N is
not within the specified range. It is possible that the im
pedance of L or N conductor is too high.
An integrated fuse is defective and must be replaced.
During loop or mains internal resistance test
If the RCD trips during mains internal resistance test,
then the neutral conductor (N) and the protective earth
conductor (PE) are transposed!
The test result is correct. The RCD has correctly tripped.
The trip time test has been interrupted because the con-
tact voltage has exceeded the limit value of 25 V.