Herunterladen Inhalt Inhalt Diese Seite drucken

Signal Inputs/Outputs On Transceiver - Siemens SIMATIC FS400 Anleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

12.1.5 Signal inputs/outputs on transceiver

Terminal 5: EDM (contactor
monitoring) *
Terminal 6:
Start/restart button *
Collective malfunction/dirt signal
Table 12.1-7: Receiver, machine interface, status and control signals
*
= The "restart interlock" and "dynamic contactor monitoring" functions are only available in the
extended mode
PG 13.5
Terminal 5
Terminal 6
Table 12.1-8: Terminal 5 and terminal 6 on PG 13.5 transceiver end cap to
Input:
Input:
Output:
Hirschmann plug
PIN 5
PIN 6
Hirschmann, MIN-style and M12 transceiver end caps.
Contacts (break) against 24 V DC
current load: max. 20 mA
Contact (make) against 24 V DC
current load: max. 15 mA
pnp: Typical 22 V DC switching,
max. 80 mA
MIN-style plug
M12 plug
(7-pin)
PIN 5
PIN 5
PIN 6
PIN 6