Cause / significance
F9
OSSD short circuit after VCC
output 2 or cross-circuit
F10*
Undervoltage on power
supply
F20
Internal fault
F21
Internal fault
F22
Internal fault
F23
Internal fault
F24
Internal fault
F25*
Different transmission
channels discovered (during
operation)
F26*
Different evaluation proce-
dures (SCAN) discovered
(during operation)
F27
Internal fault
F28
Internal fault
F29
Internal fault
F30*
Error in semiconductor test
(multifuse)
F32*
RES operating mode
changed (during operation)
F33*
EDM operating mode
changed (during operation)
F34*
EDM timeout exceeded
(feedback circuit closes or
will not open)
F35*
Start/restart button pressed
longer than 10 seconds
F36
Test identification signal from
transmitter longer than 3
seconds
F37*
EDM configuration error
F38
Internal fault
*
Locking error - a system reset is only achieved by switching the supply voltage off and on
again.
Table 11.2-2: Receiver diagnostics
Measure to eliminate error
Clear short circuit after VCC or cross-circuit, if
it occurs again send the device in
Check power supply and feed
Send the device in
Send the device in
Send the device in
Send the device in
Send the device in
Turn supply voltage off and on again
Turn supply voltage off and on again
Send the device in
Send the device in
Send the device in
Switch supply voltage off and on again, if it
occurs again send the device in
Turn supply voltage off and on again
Turn supply voltage off and on again
Check EDM wiring, turn supply voltageoff and
on again
Check the start button wiring
Check transmitter test input
Check EDM wiring, turn supply voltage on and
off again
Send the device in