RCM 880 / 890
4
Installing and Connecting the RCM 880 / 890
4.1 Installation Instructions
The site of installation should be easily accessible.
There must be sufficient air circulation around the multi sensor.
Please note the dimensions and installation dimensions ( p. 46).
4.2 Fixing the Mounting Plate
IMPORTANT
For the RCM 880 / 890 with integrated galvanic isolation module, the side with the
milled groove must face the device.
Select a suitable site of installation with sufficient space.
Screw down the mounting plate with 4-6 screws (M6).
4.3 Assembling the Connection Cable
RECOMMENDATION
A shield on both sides can prevent signal interference from electromagnetic fields.
RCM 880 / 890 without integrated galvanic isolation module
Disassemble the cable gland.
Pull the 6-wire cable (⌀ 5...10 mm) onto the union nut and the clamping insert.
Strip 45 mm
Remove the foil and supplementary wire.
Leave 10 mm
Use wire end ferrules with 8...10 mm length
wires according to the sleeves used and attach the wire end ferrules.
Technical changes reserved
of insulation from the sheath.
of the screen.
Installing and Connecting the RCM 880 / 890
(0.25...1 mm²), strip the insulation from the
- 29 -