Commissioning and Operation
5.3.1 Enter PIN
Set the PIN "0880", which is set as stand-
ard, via the operating elements and confirm
with the
button.
You can now make settings on the room
condition monitor. See also "Set New PIN"
( p. 42).
5.3.2 Set Contrast
Display menu
Set contrast
Set a value between 0 and 100%.
5.3.3 Set Backlight
Display menu
Set backlight
Set the function of the backlight:
On: Always switched on.
•
Off: Always switched off.
•
Automatic: The backlight is switched off af-
•
ter 60 s if not in use.
5.3.4 Select Units
Display menu
Select units
Changing the unit resets the temperature
history and MIN/MAX values.
Set which units are used for air pressure
and temperature:
Air pressure: hPa, mbar.
•
Temperature: °C, °F.
•
5.3.5 Set Air Humidity Output
Transmitter
Set air humidity output
Set the start and end values and the output
for air humidity.
The adjustable value range is between 0
•
and 100%r.H.
Set the requested output signal.
- 40 -