ISOMETER®107TD47
Allgemeine Daten
EMV Störfestigkeit ..................................................................................................... nach EN 61326
EMV Störaussendung ............................................................................................... nach EN 61326
Schockfestigkeit IEC60068-2-27 (Gerät in Betrieb) .......................................................15 g/11 ms
Dauerschocken IEC60068-2-29 (Transport)....................................................................40 g/6 ms
Schwingungsbeanspruchung IEC 60068-2-6 (Gerät in Betrieb)......................1 g / 10 ... 150 Hz
Schwingungsbeanspruchung IEC 60068-2-6 (Transport)................................2 g / 10 ... 150 Hz
Umgebungstemperatur (bei Betrieb)................................................................. -10 °C ... +55 °C
Umgebungstemperatur (bei Lagerung) ............................................................. -40 °C ... +70 °C
Klimaklasse nach DIN IEC60721-3-3 ..........................................................................................3K5
Betriebsart .....................................................................................................................Dauerbetrieb
Einbaulage .............................................................................................................................beliebig
Anschlussart.............................................................................................................Reihenklemmen
Anzugsdrehmoment ..................................................................0,5 ... 0,6 Nm (4,3 ... 5,3 lb-in)
Anschlussvermögen Starr / flexibel .....................................................0,2 ... 4 / 0,2 ... 2,5 mm
Anschlussvermögen Flexibel mit Aderendhülse, ohne/mit Kunststoffhülse .... 0,25 ... 2,5 mm
Leitergrößen (AWG).................................................................................................................24-12
Schutzart Einbauten (DIN EN 60529) .........................................................................................IP30
Schutzart Klemmen (DIN EN 60529) ..........................................................................................IP20
Schraubbefestigung.................................................................................................................2 x M4
Schnellbefestigung auf Hutprofilschiene..........................................................................IEC 60715
Entflammbarkeitsklasse ...................................................................................................... UL94V-0
Gewicht ca. ................................................................................................................................400 g
Bestellangaben
Typ
Type
107TD47
107TD47-133
Zubehör
Typ
Type
CMS460-D4-2
STW2
Alle Rechte vorbehalten.
Nachdruck und Vervielfältigung
nur mit Genehmigung des Herausgebers.
Änderungen vorbehalten!
©
Bender GmbH & Co. KG
Bender GmbH & Co. KG
Londorfer Str. 65
35305 Gruenberg
12
Netznennspannung U
n
Nominal system voltage U
n
AC 230 V, 50 ... 60 Hz
AC 127 V, 50 ... 60 Hz
Beschreibung
Description
Laststrom-Monitor
Load current monitor
Stromwandler/current transformer
AC 50 A/50 mA
Germany
General data
EMC immunity.........................................................................................................acc. to EN 61326
EMC emission .........................................................................................................acc. to EN 61326
Shock resistance IEC60068-2-27 (device in operation)................................................. 15 g/11 ms
Bumping IEC60068-2-29 (during transport) .................................................................. 40 g/6 ms
Vibration resistance IEC 60068-2-6 (device in operation)................................ 1 g / 10 ... 150 Hz
Vibration resistance IEC 60068-2-6 (during transport).................................... 2 g / 10 ... 150 Hz
Ambient temperature (during operation)...........................................................-10 °C ... +55 °C
Storage temperature range..................................................................................-40 °C ... +70 °C
Climatic class acc. to DIN IEC60721-3-3 .....................................................................................3K5
Operating mode .............................................................................................. continuous operation
Mounting........................................................................................................................ any position
Connection................................................................................................................ screw terminals
Tightening torque, terminal screws .......................................... 0.5 ... 0.6 NM (4.3 ... 5.3 lb-in)
2
Connection rigid, flexible .....................................................................0.2 ... 4 / 0.2 ... 2.5 mm
2
Connection flexible with connector sleeve, without/with plastic sleeve............0.25 ... 2.5 mm
Conductor sizes (AWG) ...........................................................................................................24-12
Protection class, internal components (DIN EN 60529) ...........................................................IP30
Protection class, terminals (DIN EN 60529)................................................................................IP20
Screw fixing .............................................................................................................................2 x M4
DIN rail mounting acc. to ..................................................................................................IEC 60715
Flammability class............................................................................................................... UL94V-0
Weight approx...........................................................................................................................400 g

Ordering details

Versorgungsspannung U
s
Supply voltage U
s
AC 230 V, 50 ... 60 Hz
AC 127 V, 50 ... 60 Hz
Accessories
Tel.: +49 6401 807-0
Fax: +49 6401 807-259
Art.-Nr.
Art. No.
B 92 016 003
B 92 016 004
Art.-Nr.
Art. No.
B94053030
B942709
All rights reserved.
Reprinting and duplicating
only with permission of the publisher.
Subject to change!
©
Bender GmbH & Co. KG
E-Mail: info@bender.de
www.bender.de
107TD47_D00091_00_M_DEEN / 10.2016
2
2

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis