7.2. LCD DISPLAY FUNCTIONS.
When starting up the UPS, the display shows the default UPS
status summary screen.
Main menu
Submenu
Status of the
UPS
Event log
Measurements
Bypass step
Load segment
Start battery
Start WLAN
End WLAN
Control
Reset fault
Config, Autom
Reset event
Reset built-in
Restore factory
Settings
Identification
Table 12. Default UPS states.
7.3. USER SETTINGS.
Submenu
Password
It can be changed by the user.
Language
English, Italian, French, German, Spanish,
change.
Polish, Catalan, Galician, Basque, Portuguese
User password
[Enabled, ****], [Disabled]
Audible alarms
[Enabled], [Disabled]
Output voltage
[200 V], [208 V], [220 V], [230 V], [240 V]
USER MANUAL
Display information or
menu function
UPS mode, IoT status, date/time,
battery status, and current alarms.
Displays stored events and faults.
[Load] W VA A P%, [Input/Output] V Hz,
[Battery] % min V EBM, [DC Bus] V,
[Temperature] C
Transfer from UPS to bypass mode
Load segment on/off
Start manual battery test
test
If the WLAN status is in configuration
mode, the available option would
settings
be "Finish WLAN configuration";
otherwise, the available option would
settings
be "Start WLAN configuration".
Clear active fault.
status
The UPS will automatically reassign
the BMS address when set to "yes";
BMS
otherwise, it will do nothing.
Clear events and faults.
list
Reset the IoT and Modbus TCP function
IoT
on the UPS.
Restore to factory default settings
settings
View user configuration
[Product type], [Model], [Serial
number], [UPS firmware], [Embedded
IoT firmware], [Embedded Ethernet IP],
[WLAN IP], [Embedded Ethernet MAC],
[WLAN MAC]
Available settings
Submenu
Output
frequency
High efficiency
mode
Auto Bypass
Load segments
Cold start/Auto
re-start/Start
on bypass
Wiring failure
Overload pre-
alarm
Dry In signal
Dry out signal
Ambient
temperature
alarm
Remaining
battery time
Date and time
Time zone
LCD contrast
Default
settings
Modbus TCP
0000
Enable internal
IoT
English
Table 13. User settings.
[Disabled]
[Disabled]
[230 V]
Available settings
[Normal automatic detection], [50 Hz,
60 Hz converter]
[Enabled], [Disabled]
[Enabled], [Disabled]
Auto start delay:[No delay][1-99999s]
Auto shutdown delay: [Disable],
[0-99998s]
Cold start: [Disabled], [Enabled]
Default settings: Enabled = unit start-up
via batteries is permitted (only when
mains power is unavailable).
Other options: Disabled = battery start-
up not permitted.
Auto restart: [Disabled], [Enabled]
Default settings: Enabled = the UPS will
restart in Normal mode after network
recovery if the UPS has shut down due
to battery voltage below the cut-off
level.
Other options: Disabled.
Bypass startup: [Disabled], [Enabled]
Default settings: Disabled = the UPS will
start up directly in On-Line mode.
Other options: Disabled = the UPS will
start in Bypass mode, remain in it for
5 seconds, and then transfer to On-Line
mode.
[Enabled], [Disabled]
[50%÷105%]
[Disabled], [Remote activated],
[Remote deactivated], [Force bypass],
[Remote MBP]
(2)
[powered load], [on battery],
[low battery], [open battery], [bypass],
[UPS OK]
[Enabled], [Disabled]
[Enabled], [Disabled]
dd/mm/aaaa hh:mm
Set time zone
[0-100%]
[Enabled], [Disabled]
[Yes], [No]
SLC TWIN RT3 LION UNINTERRUPTIBLE POWER SUPPLIES (UPS)
Default
settings
Normal
50 Hz/60 Hz
automatic
detection
[Disabled]
[Disabled]
3 s disabled
Cold start:
enabled
Automatic
restart:
enabled
Bypass
startup:
disabled
[Disabled]
105%
[Remote MBP]
[on battery]
[Disabled]
[Disabled]
01/01/2025
00:00
GMT+1
50%
[Disabled]
[Yes]