F i g u r e 1 - 1 4 .
Tw o - P o s t , O p e n - F r a m e R e l a y R a c k W i d e - H o l e S p a c i n g
44 mm (1.75 inches) (1 U)
To mark the rack, perform the following steps:
Place a mark on the rack's front vertical rails where you want to locate the bottom of
1
the system you are installing in the two-post rack.
The bottom of each 1-U space is at the middle of the narrowest metal area between
holes.
NOTE: If your rack has wide-hole spacing, go to step 3.
Place a mark 88 mm (3.5 inches) above the original mark you made (or count up six
2
holes in a rack with universal-hole spacing (see Figure 1-13).
Each 1-U (44 mm, or 1.75 inches) of vertical space on a rack with universal-hole
spacing has three holes with center-to-center spacing between holes (beginning at the
top of a 1-U space) of 0.625, 0.625, and 0.5 inches (see Figure 1-13).
NOTE: If your rack has universal-hole spacing, you have completed the procedure for
marking the rack.
Place a mark 88 mm (3.5 inches) above the original mark you made (or count up to the
3
fourth hole in the rack with wide-hole spacing (see Figure 1-14).
Each 1-U (44 mm, or 1.75 inches) of vertical space on a rack with wide-hole spacing
has two holes with center-to-center spacing between holes (beginning at the top of a
1-U space) of 31.7 mm (1.25 inches) (see Figure 1-14).
12.7 mm (0.5 inch)
31.7 mm (1.25 inches)
Rack Installation Guide
1-21