OPERATION
Settings
Example
Daytime
Room temperature
outside
temper-
atures
too cold
+5 °C to
Increase "Base point flow
+15 °C
temperature heating curve"
(03-001)
-15 °C to
Increase "VLT at standard
+5 °C
outside temperature heating
curve" (03-013)
f Record the adjustments in the table:
Date
Heating curve
03-001
s
s
s
s
Date
Cooling curve
03-043
s
s
s
s
Heating curve
Heating circuit flow temperature
°C
70
Design flow temperature
65
(03-013)
60
55
50
45
40
35
30
25
20
15
10
5
-20
-15
-10
-5
1 Modified heating curve if the low end temperature (03-
001) is increased.
2 Standard heating curve set on commissioning.
3 Modified heating curve if the design flow temperature
(03-013) is reduced.
28 |
too hot
Reduce "Base point flow
temperature heating curve"
(03-001)
Reduce "VLT at standard
outside temperature heating
curve" (03-013)
Note
03-013
s
s
s
s
Note
03-048
s
s
s
s
1
2
3
Low end tempera-
ture (03-001)
°C
0
5
10
15
20
Outside temperature
Cooling curve
Cooling curve
TV [°C]
1
20°C
TV
Flow temperature
OT
Outside temperature
1 03-043 low end flow temperature, cooling mode
2 03-048 Flow temperature at standard outside
temperature
3 03-047 Standard outside temperature
Dew point limit
When cooling, the minimum flow temperature is limited. The
limit (dew point) is calculated by the heat pump controller from
the following variables:
- Current room temperature
- Current relative humidity in the room
If no room temperature value is available, the current outside
temperature is used. If no relative humidity value is available,
the dew point temperature is calculated using a relative hu-
midity figure of 60 % as a default value.
Room temperature and room humidity are captured by the
room programming units or the WP-RT Touch.
Property damage
!
Improper settings on the cooling curve can cause
damage to the system (due to condensation).
f Make changes to the cooling curve only by agree-
ment with your contractor.
5.6.1 Adjusting the heating and cooling curve
f On the start screen, press the selection button.
f Open the menu.
Menu
Heating circuit  / Settings  / Heating curve  / Base point temperature
heating curve
Heating circuit  / Settings  / Cooling curve  / Base point temperature
cooling curve
f Adjust the temperature by turning the selection button.
f Save the settings by pressing the selection button.
f Return to the start screen by pressing the ESC button a
number of times.
Dew point limit
2
TA [°C]
3
OTE