Program settings
Program setting of POOL 310 can be performed via the
start guide or directly in the menu system.
MENU SYSTEM
If you do not make all settings via the start guide or need
to change any of the settings, this can be done in the
menu system.
START GUIDE
The start guide appears at initial start-up after heat pump
installation, but can also be found in menu 7.7.
MENU 7.2.1 - ADD/REMOVE ACCESSORIES
Here, you state which accessories are installed for the
compatible product.
To identify connected accessories automatically, select
"Search for accessories". It is also possible to select ac-
cessories manually from the list.
MENU 7.2.17 - POOL
Activate/Deactivate Pool
start temp
Setting range: 5,0 – 80,0 °C
stop temperature
Setting range: 5,0 – 80,0 °C
Desired charge power
Setting range: 1-100 kW
Activate/Deactivate: Here, you activate or deactivate
pool heating.
Start and Stop temperature: Here, you set the start and
stop temperature of pool heating.
Desired charge power: Here, you select the desired
charge power to the pool.
NOTE
The same settings can be made for Pool 2.
Caution
The start temperature cannot be set to a value
that is higher than the stop temperature.
MENU 7.1.2.2 - PUMP SPEED HEATING
MEDIUM GP1
Make settings here for the heating medium pump's
speed in the current operating mode, for example in
heating or hot water operation. Which operating modes
can be changed depends on which accessories are
connected.
Minimum permitted speed
POOL 310 | GB
Setting range: 1 - 50 %
Speed in standby mode
Setting range: 1 - 100 %
Pool, auto
Alternative: on/off
Pool, manual
Setting range: 1 - 100 %
Highest permitted speed
Setting range: 50- 100%
Minimum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a lower speed than the set value.
Speed in standby mode: Here, you set the speed the
heating medium pump will have in standby mode.
Standby mode occurs when heating operation is permit-
ted but there is no need for either compressor operation
or electric additional heat.
Pool, auto: Here, you set whether the heating medium
pump is to be regulated automatically or manually.
Pool, manual: If you have opted to control the heating
medium pumps manually, you set the desired pump
speed here.
Maximum permitted speed: Here you can restrict the
pump speed so that the heating medium pump is not
allowed to operate at a higher speed than the set value.
Caution
Also see the Installer Manual for the indoor
module.