malfunction and lock cause diagnostics
In the event of a burner lock-out, the red light on the reset button will be fixed.
Holding the reset button down for more than 3 seconds, the diagnostics phase will be activated (quick flashing red light). The table below
lists the meaning of the malfunction or lock-out cause depending on the number of blinks (always red-coloured).
Holding the reset button down for at least 3 seconds, the diagnostics function will be interrupted (for further details see technical sheet
7614).
The diagram below indicates the operations that are necessary to activate diagnostics functions.
Visual indication
2 blinks
●●
3 blinks
●●●
4 blinks
●●●●
5 blinks
●●●●●
6 blinks
●●●●●●
7 blinks
●●●●●●●
8 blinks
●●●●●●●●
9 blinks
●●●●●●●●●
10 blinks
●●●●●●●●●●
14 blinks
●●●●●●●●●●●●●●
- Under fault diagnosis conditions the device remains deactivated. The burner is off.
- The «AL» alarm signal is on terminal 10 that is under voltage. To reactivate the device and start a new cycle, press the reset button for
1 sec. (< 3 sec).
" AL" to terminal 10
No flame at the end of the"TSA" (safe ignition time)
- Faulty or soiled fuel valves
On
- Faulty or soiled flame detector
- Poor adjustment of burner, no fuel
- Faulty ignition equipment
defective "LP" (air pressure switch)
On
- No or faulty air pressure signal after completion "t10"
- LP pressure switch contact welded in standby position
On
Extraneous light during the ignition phase
Time out "LP" - "LP" is welded into working position
On
- "LP" is welded in work position
On
Not used
Too many losses of flame during operation (limitation of repetitions)
- Faulty or soiled fuel valves
On
- Faulty or soiled flame detector
- Poor adjustment of burner
On
Not used
On
Not used
Off
Wiring problems or damage inside the device
Off
CPI contact not closed
12 / 20
0006080763_201306
Possible causes