With the manifold type S300/S200/S60-SS/ S203-SS...(material: stainless steel) additional toxic and cor-
rosive gases which is stores inside gas cylinder or bundle with over pressure can be reduced from maximum
300 bar tubing pressure (3 bar, 6 bar, 10 bar, 14 bar, 28 bar, 50 bar, 100 bar, 200 bar).
EN
A relief valve at pressure regulator secures the manifold with its outlet pressure against incorrect pressure
rising at the outlet due to leakage in regulator seat. Additional components could be safety valve and/ or
check valve.
The real inlet and outlet pressure of the manifold is displayed at the pressure gauges. There is the possibility
to use contact gauges for inlet and outlet pressure.
If the manifold has the opportunity for process gas purging, this can be done before initial start-up to remove
contaminates. Furthermore it is possible to depressurize the high pressure side before cylinder is changed.
If the manifold has the opportunity for inert gas purging (S203), the high pressure area of the manifold can
be purged to remove contaminates before initial start-up or before cylinder or bundle change. The manifold
version with inert gas purging is only available in stainless steel.
The described system is mounted on a stainless steel plate. Due to plate dimensions all components are
protected against damage inside of package, during transport and in mounted condition. The two plates
design enables to mount the component easy and with less weight.
The cut-outs in the front plate enable to change the gauge without disassembly of the complete manifold. At
the back plate at both sides are holes to connect the cylinder hoses with carabiner hook. To connect ground-
ing you can fi nd screw at the ground plate.
The development, construction and production testing is according to the following standards:
- Regulators- ISO 7291
- Valves- ISO 10297
- Gauges EN 837-1
- Mechanical explosion prevention of complete manifold- ISO80079-36; IEC 60079-32-1; TRGS 727
5. TRANSPORT, PACKAGING AND STORAGE
TIPS AND
The installation and start- up of this gas supply panel is normally done by the supplier or by authorized
personnel.
Even though there can be some users or maintenance personnel who care about the packaging. The fol-
lowing notes should be observed accordingly.
5.1. SAFETY INFORMATION FOR TRANSPORTATION
NOTE!
Damages caused by inappropriate transportation!
If transported inappropriately, consignments can fall or topple over. This can cause considerable property
damage.
When unloading the consignments on delivery and transporting them on the premises, act with caution
and observe the symbols and warnings on the packaging.
Use only the attachment points provided.
Do not remove the packaging until you are ready to assemble the regulator.
5.2. TRANSPORT INSPECTION
Upon delivery, check immediately that the consignment is complete and has not been damaged during tran-
sit. Procedure on detection of visible transport damage:
Refuse acceptance of the delivery or only accept subject to reservation
Record the extent of the damage on the transportation documentation or on the forwarder's delivery note
File a complaint
TIPS AND RECOMMENDATIONS!
Report each and every defect as soon as you discover it. Claims for damages can only be asserted within
the specifi ed periods.
RECOMMENDATIONS!
18/380