Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .............................................................................................................................. 3M4
Transport (IEC 60721-3-2) ..................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1) ...................................................................................................................... 1M3
Connection
Connection type................................................................................................................................Push-wire terminal
Nominal current....................................................................................................................................................≤ 10 A
Conductor sizes............................................................................................................................................. AWG 24-14
Stripping length....................................................................................................................................................10 mm
rigid ..........................................................................................................................................................0.2...2.5 mm²
flexible without ferrules........................................................................................................................ 0.75...2.5 mm²
flexible with ferrules, with/without plastic collar ............................................................................... 0.25...2.5 mm²
Multiple conductor, flexible with TWIN ferrule with plastic sleeve.......................................................0.5...1.5 mm²
Opening force........................................................................................................................................................... 50 N
Test opening, diameter....................................................................................................................................... 2.1 mm
Other
Operating mode ........................................................................................................................... Continuous operation
Mounting .................................................................................................... Cooling slots must be ventilated vertically
Degree of protection, built-in components (DIN EN 60529) ................................................................................. IP30
Degree of protection, terminals (DIN EN 60529) .................................................................................................... IP20
Enclosure material .................................................................................................................................... Polycarbonate
DIN rail mounting acc. to................................................................................................................................. IEC 60715
Screw fixing ......................................................................................................................... 2 x M4 with mounting clip
Weight ................................................................................................................................................................ ≤ 150 g