Herunterladen Diese Seite drucken

Hitachi SET FREE-Serie Bedienungsanleitung Seite 32

Vorschau ausblenden Andere Handbücher für SET FREE-Serie:

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 131
PIPING WORK AND REFRIGERANT CHARGE
Ⓑ First branch
outdoor unit HP
5-10
12-16
18-24
26-54
56-96
Ⓒ Multi-Kit after first branch
total indoor unit HP
<12
12-17.99
18-25.99
26-55.99
≥ 56
Ⓓ Header branch
number of header
total indoor unit HP
branches
5-8
5-10
 Diameter of the main pipe (from the base of the unit or
connection kit 1 to the first branch).
equivalent pipe length < 100 m
outdoor unit (HP)
5
(6/8)
10
(12/14)
16
(18-24)
(26-34)
(36-54)
(56-66)
(68-72)
(72-88)
≥ 90
?
n o t e
When the maximum length of the equivalent refrigerant pipe from the
piping connection kit 1 to the indoor unit is over 100m, the pipe size
of gas and liquid lines from the piping connection kit 1 to first branch
should be increased by one size with reducers (field-supplied).
22
PMML0479 rev.2 - 02/2018
model
E-102SN4
E-162SN4
E-242SN3
E-302SN3
MW-NP2682A3
model
E-102SN4
E-162SN4
E-242SN3
E-302SN3
MW-NP2682A3
model
4
E-102SN4
8
E-162SN4
Gas
liquid
ø15.88
ø9.52
ø19.05
ø9.52
ø22.20
ø9.52
ø25.40
ø12.70
ø28.58
ø12.70
ø28.58
ø15.88
ø31.75
ø19.05
ø38.10
ø19.05
ø44.45
ø19.05
ø44.45
ø22.20
ø50.80
ø22.20
ø50.80
ø25.40
 Pipe diameter after first branch or between Multi-Kits in the
main branch.
total indoor unit capacity after the
first branch (HP)
< 6
(6-8.99)
(9-11.99)
(12-15.99)
(16-17.99)
(18-25.99)
(26-35.99)
(36-55.99)
(56-67.99)
(68-73.99)
(74-89.99)
≥ 90
?
n o t e
In the case that the piping length from the Multi-Kit at the first branch
to the terminal indoor unit is over 40m, the size of the main piping
should be increased by one size with reducers (field-supplied). Refer
to "Piping Branch Restriction" for details.
Even if the equivalent refrigerant piping length is more than 100m, no
need to increase the pipe size after first branch. If the Multi-Kit size is
larger than the first branch, adjust the Multi-Kit size to the first branch.
In case that the selected pipe size after the first branch is larger than
the pipe size before the first branch, use the same pipe size as before
the branch.
 Pipe diameter between Multi-Kit and indoor unit.
indoor unit (HP)
(0.4-1.5)
2.0
(2.5-6.0)
8.0
10.0
16.0
20.0
?
n o t e
(*): When the liquid piping length is longer than 15m, use ø9.52 pipe
and reducer (field-supplied).
The pipe diameter should be the same as the indoor unit piping
connection size.
Check the corresponding Indoor unit connection sizes.
Gas
liquid
ø15.88
ø9.52
ø19.05
ø9.52
ø22.20
ø9.52
ø25.40
ø12.70
ø28.58
ø12.70
ø28.58
ø15.88
ø31.75
ø19.05
ø38.10
ø19.05
ø44.45
ø19.05
ø44.45
ø22.20
ø50.80
ø22.20
ø50.80
ø25.40
Gas
liquid
ø12.70
ø6.35(*)
ø15.88
ø6.35(*)
ø15.88
ø9.52
ø19.05
ø9.52
ø22.20
ø9.52
ø28.58
ø12.70
ø28.58
ø15.88

Werbung

loading