Herunterladen Diese Seite drucken

SEW-Eurodrive MOVIDRIVE technology Betriebsanleitung Seite 49

Applikationsumrichter
Vorschau ausblenden Andere Handbücher für MOVIDRIVE technology:

Werbung

Model (frame size)
MDX9.A-0840-2.3-4-.. (6)
MDX9.A-1080-2.3-4-.. (6)
5.3.4
Motor overload protection
The units are provided with load and speed-sensitive overload protection and thermal
memory retention upon shutdown or power loss.
The trip current is adjusted to 150% of the rated motor current.
5.3.5
Surrounding air temperature rating
For surrounding air temperature rating, refer to chapter "General technical data".
5.3.6
Derating
For derating, refer to chapter "Selecting an inverter" of the product manual.
5.3.7
Other ratings
Type rating
Pollution degree
Max. altitude
5.3.8
Wiring diagrams
For wiring diagrams, refer to chapter "Wiring diagrams".
Three-phase 200 – 240 V voltage range (SCCR: 65 kA)
Non-semiconduc-
Inverse-time circuit brea-
tor fuses (cur-
ker (currents are maxi-
rents are maxi-
mum, voltages minimum
mum values)
225 A/240 V
Class: J, T
225 A/240 V
Class: J, T
Elektrische Installation
Type E combination motor
controller, mfd by Siemens,
values)
225 A/240 V
225 A/240 V
Open type
2
2000 m
Betriebsanleitung – MOVIDRIVE
UL-gerechte Installation
type Sirius
(rated 480 V/277 V)
3RV2041-4YA10, 93 A
3RV2041-4YA10, 93 A
®
technology
5
49

Werbung

loading

Diese Anleitung auch für:

Movidrive