Herunterladen Inhalt Inhalt Diese Seite drucken

External Connections (Connection Board); Before Starting The System - SystemAir SAVE VSR 150/B Betriebs- Und Wartungsanleitung

Vorschau ausblenden Andere Handbücher für SAVE VSR 150/B:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 96
GB
Position
13
14
15
16
17
3.2

External connections (Connection board)

External connections to the main circuit board are done via connection board situated inside of the unit.
Position
Description
1
Connection to the main circuit board
2
Connection for external control panel (HMI) or Internet access module (IAM)
3
Modbus RS485 connection
AI6–7
Freely configurable Analog input. None/Input type selection in HMI.
DO1–4
Freely configurable Digital output. None/Output type selection in HMI.
AO3–5
Freely configurable Analog output. None/Output type selection in HMI. Actuator type 0–10V, 10–
0V, 2–10V, 10–2V.
UI1–5
Freely configurable Universal input. Can be configured to act as Analogue input (0–10V) or as
Digital input (24V). None/Input type selection in HMI (NC or NO polarity).
24V
Maximum current 200mA at 24VDC +-10%.
4

Before starting the system

When the installation is finished, check that:
• The unit is installed in accordance with the instructions
• The unit is correctly wired
• Outdoor and exhaust air dampers and silencers are installed and that the duct system is correctly connected to the
unit
• All ducts are sufficiently insulated and installed according to local rules and regulations
• Outdoor air intake is positioned with sufficient distance to pollution sources (kitchen ventilator exhaust, central vac-
uum system exhaust or similar)
| v01_1.8.0
Description
Digital input 2 — Freely configurable / Cooker hood (VTR 150/K unit)
Analog output 2 — Freely configurable / Electrical heater controller (VTC 700 unit)
Analog output 1 — Rotor of the heat exchanger (VSR, VTR units) / Damper control
(VTC units)
Terminals for speed control of extract air fan
Terminals for speed control of supply air fan
Fig. 3 External connection box and board
Before starting the system |
9

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis