6.4

Tabelle Fehlercodes

Communication error
(Checksum, ...)
Length of written SPDU is wrong
Reading an unimplemented SPDU
Writing to an unimplemented SPDU
Reading Index 2
Writing to a read only SPDU
Writing an unimplemented System Command
Distance between two tought points too small
Written parameter out of defined range
6.5

Tabelle Werkseinstellungen

Application Specific Name
Switching points work
Measuring range work
Average
Output function switching output
Nominal value
quality parameter
BA_FADK14IO-Link_V01-02-11_DE.doc
04.12.2012/rek
0XA5
Transfer of the measuring range from the interim register to the working register
0XE0
Save all parameters in Flash memory
0x10
0x00
0x10
0x00
0x80
0x11
0x80
0x11
0x80
0x23
0x80
0x23
0x80
0x23
0x80
0x40
0x80
0x30
0X18
empty
0X40
Switching point A: 50mm
Switching point B: 400mm
0X42
Measuring range limit A: 50mm
Measuring range limit B: 400mm
0X50
0 (keine Mittelung)
0X62
0 (Alarm)
0X65
7
Communication error, No details
Communication error, No details
Device error, Index not available
Device error, Index not available
Device error, Access denied
Device error, Access denied
Device error, Access denied
Device error, Interfering parameter
Device error, Parameter value out of range