ELECTRICAL WIRING

Refrigerant Cycle Number Setting
DSW4
Setting position
(Setting for the ten digit).
RSW1
Setting position.
(Setting for the last digit).

DSW5: Transmission Setting of End Terminal
Resistance
Setting before shipment
10.3 COMMON WIRING
!
C A U T I O N
All the field wiring and electrical components must comply with local
codes.
10.3.1 Electrical wiring between indoor unit
and outdoor unit
Connect the electrical wires between the indoor unit and the
outdoor unit, as shown below.
Follow local codes and regulations when performing
electrical wiring.
If the refrigerant piping and the control wiring are connected
to the units in the same refrigerant cycle.
Use twist pair wire (more than 0.75 mm²) for operation wiring
between outdoor unit and indoor unit, and operation wiring
between indoor unit and indoor unit.
Use 2-core wire for the operating line (Do not use wire with
more than 3 cores).
Use shielded wires for intermediate wiring to protect the
units from noise obstacle at length of less than 300 m and
size complied with local code.
Open a hole near the connection hole of power source
wiring when multiple outdoor units are connected from one
power source line.
The recommended breaker sizes are shown in Table of
electrical data and recommended Wiring, Breaker Size/1 O.U.
In the case that a conduit tube for field-wiring is not used, fix
rubber bushes with adhesive on the panel.
All the field wiring and equipment must comply with local and
international codes.
H-LINK twist pair shielded cable must be grounded in the
outdoor unit side.
13
PMML0394B rev.0 - 11/2015

DSW6: Function setting (RAS-3HVRNM2E) (No
setting is required)
Power source setting
(RAS-(4-6)H(V)RNM2E and RAS-(4-6)H(V)RNS2E)
(Setting is required)
Power source setting

JP1~6: Jumper cable
JP1 cut: Fixing Cooling Mode
JP5 cut: Alternative Defrosting
No setting is required
JP6 cut: High-Pressure Control Based on
R407C Piping
!
C A U T I O N
Pay attention to the connection of the operating line. Incorrect connection
may cause the failure of PCB.